Product Description:
ZGLEDUN Series LDCJX2AC contactors are mainly used for AC 50Hz or 60Hz, voltage highest up to 690V, and rated working current up to 95A in AC-3, 400V (380V) circuits for remote connection and disconnection of circuits, and frequent starting. It is used to control AC motors, and can be combined with appropriate thermal relays to form an electromagnetic starter to protect circuits that may be overloaded.
Meet the standards – GB14048.4, IEC60947-4-1.
Working and Installation Conditions:
The ambient air temperature is -5℃~+40℃, the average value within 24 hours does not exceed +35℃
Altitude: not more than 2000 m
Atmospheric conditions: when the highest temperature is +40℃, the relative humidity of the air does not exceed 50%. Higher relative humidity is allowed at lower temperatures.For example, up to 90% at 20℃. Special measures should be taken for the occasional condensation due to temperature changes.
Pollution degree: Level 3
Installation category: Class III
Installation conditions: the inclination of the installation surface and the vertical surface is not more than +-5°
Shock and vibration: The product should be installed and used in a place where there is no significant shaking, shock and vibration.
Measurements (mm) :