Product Description:
ZGLEDUN LDSCB series product is a SPD dedicated surge backup protector. It can effectively solve the fire hazard caused by the deterioration of the lightning protector and the power grid failure, and solve the failure of the lightning protector caused by the malfunction of the backup protection device caused by lightning. This backup surge protector ensures that the surge protector (SPD) does not catch fire, and the equipment lightning protection continues to be effective. At present, fuses or circuit breakers are widely used in coordination with SPD. When SPD fails or short-circuits, it will cause fire. Seies LDSCB is specially designed for SPD. It will not break under a large lightning strike. But it can be quickly broken when small power frequency current occurs after SPD failure.
Features:
◆SCB can achieve selective breaking of the passed power frequency current and lightning current, which can effectively protect the SPD surge protector due to deterioration that causes the SPD start voltage to drop below the power supply voltage, and the power frequency leakage current increases, causing serious fire accidents.
◆ When the SPD has lightning current passing through, the SGB connected in series at the front of the SPD can ensure that the lightning current will not trip, damage, and the lightning protection will continue to be effective;
◆The UP Value (voltage protection level value) of SCB is very low when passing thunder current;
◆Using parameter control trip mechanism, and installation with 35mm guide rail .
Main Technical Parameters | |||||
Model | LDSCB-20 | LDSCB-40 | LDSCB-60 | LDSCB-80 | LDSCB-100 |
Non-tripping Shock Wave (le) | 20kA(8/20μs) | 40kA(8/20μs) | 60kA(8/20μs) | 80kA(8/20μs) | 100kA(8/20μs) |
Rated Current In | 10kA(8/20μs) | 20kA(8/20μs) | 30kA(8/20μs) | 40kA(8/20μs) | 60kA(8/20μs) |
Residual Pressure Up | < 200V | < 300V | < 400V | < 600V | < 600V |
Rated Operational Voltage Ue | 120V/230V/400V AC | ||||
Residual Pressure Up 20kA(8/20μs) | < 300V | ||||
Current Trip Value lo (Instantaneous) | 2A±5%(2~5A) Optional | ||||
Power Frequency Load Current Breaking Time (To) | < 0.1s | ||||
Power Frequency Current Delay Trip | 500mA-3A Optional Current (is not standard and selected by the customer ) | ||||
Power Frequency Current Delay Trip Time | 1s~120s Optional Time (is not standard and selected by the customer) | ||||
Test Button | Verification of the tripping system (once a month) | ||||
Shell Protection Level | IP20 | ||||
Crimping Screw | M6 | ||||
Installation Location | Installed on front of SPD | ||||
Connecting Wire Section | 4-16mm2 | ||||
Protection Action Due to Ambient Temperature | Switch between -25℃ and +60℃ | ||||
Storage Environment | Temperature -40℃~75℃ Relative humidity <95% (below 25℃) | ||||
Working Environment | Temperature -25℃-60℃ Relative humidity <95% (below 25℃) |